YMCA Therapy Pool Inspection Report

37 – other violations of the chapter

Points: 1

Corrected during inspection?: No

Repeat: No

Inspector Notes: .17(2): Observed calcium hardness chemical value of 70 ppm at time of inspection, which is lower than minimum level operating parameter of 150 ppm. Discussed with Frank Godwin to raise Calcium Hardness to ideal range of 200-400 ppm. Calcium hardness is to be within minimum/maximum range of 150-1000 ppm prior to pool opening. See remarks below.